Techno Press
Techno Press

Structural Engineering and Mechanics
  Volume 51, Number 2, July25 2014 , pages 215-228
DOI: https://doi.org/10.12989/sem.2014.51.2.215
 


Performance of partial strength connection connected by thick plate between column flanges
Mahmood M. Tahir, Irwan Juki, Mohd Y. Ishak, Shahrin Mohammad, Abdullah Z. Awang and Roger Plank

 
Abstract
    Traditional beam connections to the minor axis of a column have relatively low strength and stiffness. A modified detail, using a plate welded between the toes of the column flange - referred to as a toe plate connection - is examined in this paper. The results of an experimental investigation for both flush and extended end-plate connections connected to a 25 mm thick end-plate are presented. The tests are complemented by finite element modelling which compares very well with the test observations. The results show a significant increase in both moment resistance and initial stiffness for this connection detail compared with connections made directly to the column web. This offers the prospect of more optimal solutions taking advantage of partial strength frame design for the minor axis as well as major axis.
 
Key Words
    flush end-plate connection; extended end-plate connection; minor axis; partial strength; finite element analysis
 
Address
Mahmood M. Tahir, Mohd Y. Ishak, Shahrin Mohammad, Abdullah Z. Awang : UTM Construction Research Centre (UTM CRC), Faculty of Civil Engineering, Universiti Teknologi Malaysia, 81310 Johor Bahru, Johor, Malaysia
Irwan Juki : Faculty of Civil Engineering, Universiti Tun Hussein Onn, Beg Berkunci 101, Parit Raja, 86400 Batu Pahat, Johor, Malaysia
Roger Plank : University of Sheffield, Western Bank, Sheffield, South Yorkshire S10 2TN, UK
 

Techno-Press: Publishers of international journals and conference proceedings.       Copyright © 2026 Techno Press
P.O. Box 33, Yuseong, Daejeon 305-600 Korea, Tel: +82-42-828-7996, Fax : +82-42-828-7997, Email: admin@techno-press.com